To configure a V2000 controller's doors, use the setup panel of the relevant Door (V2000) object: go to the Settings dialog box, click the Hardware tab, select the relevant parent VertX V2000 NC/RI object, and browse its object subtree.
To configure the doors:
- Go to the Door (V2000) object's setup panel.
- If the REX switch is enabled, select the REX Enabled checkbox (1).
- Configure the REX switch limits (see Section Configuring EEPROM ) (2).
- In the REX debounce time, msec field, enter the time period (in milliseconds) to be used for fixing (debouncing) the bouncing REX switch signal(3).
- If the door switch is enabled, select the Door switch enabled checkbox(4).
- Configure the door switch limits (see Section Configuring EEPROM ) (5).
- In the Door switch debounce time, msec field, enter the time period (in milliseconds) to be used for fixing (debouncing) the bouncing door switch signal (6).
- In the Position field, select the position of the door (7).
- In the Door priority level field, use the up and down buttons to set the door priority level (8).
- In the Norm. grant access time, msec field, enter a time period (in milliseconds). This is the time period during which the door allows access, in normal access mode (9).
- In the Ext. grant access time, msec field, enter a time period (in milliseconds). This is the time period during which the door allows access, in extended access mode (10).
- To use the door in extended access mode, select the Use extended access mode checkbox (11).
- In the Min open time, msec field, enter the minimum time period allocated for opening the door (12).
- In the Door held time, msec field, enter a time period (in milliseconds). This the time during which the door's lock is kept open after entry (13).
- In the REX open time, msec field, enter the time period (in milliseconds) allocated for opening the door with the REX switch (14).
- Select the required radio button from the REXUD option radio button group: REX unlocks door - only the REX switch can unlock the door; REX permits door to be unlocked manually - allows the door to be unlocked manually as well (15).
- Click Apply to save the changes (16).
- Configure the door strike relay:
- Under the Door (V2000) object, find the Door strike relay object. Go to the setup panel of the Door strike relay object.
- In the Minimum open time, msec field, enter a time period (in milliseconds). This is the minimum time period during which the door strike relay is open (1).
- Click Apply to save the changes (2).
- Under the Door (V2000) object, find the Door strike relay object. Go to the setup panel of the Door strike relay object.
The doors are now configured.