To set the HID integration module parameters:

  1. Go to the VertX / Edge ACS object setup panel.
  2. In the Listening port field, enter a port number. This is the port to which HID controllers connect (1).

    Note

    The default port number for HID controllers is 4070. If you need to change the port number, enter a new port number and save the configuration (see Managing the HID configuration).

  3. In the Status check interval, sec field, enter a time period (in seconds). This is the time period between two consecutive status checks of the connected devices (2).
  4. In the Controller connect timeout, sec field, enter a time period (in seconds). When this time period elapses, the system stops waiting for the controller response and assumes that the controller is disconnected (3).
  5. In the Controller get configuration timeout, sec field, enter a time period (in seconds). If the connection to a controller is lost, the system tries to get the controller's configuration and stops when the time period elapses (4).

    Note

    When getting the configuration of multiple controllers, the entered time is added together.
  6. Click Apply to save the changes (5).

The HID integration module parameters are now set.