The configuration of FS5100 panel lines is carried out on the setting panel of the Line object. This object is created on the basis of the FS5100 panel object on the Hardware tab of the System settings dialog box while constructing the UniPos 4000/5000 FSA object (see Construction of the UniPos 4000/5000 FSA object tree).

Configuration of FS5100 panel lines is carried out the following way:

  1. Go to the setting panel of the Line object.
  2. To stop line inquiry set the Disabled checkbox (1).
  3. To check remote sensors set the Remote sensors check checkbox (2).
  4. In the Amount of checks field set the amount of checks after which the condition of fire will be confirmed. Number of checks can vary from 1 to 3 (3).
  5. In the Time of transition from 1 to 2: field set the time of transition from FIRE CONDITION STAGE I to FIRE CONDITION STAGE II (in seconds) ( 4).
  6. In the Status 1: field set threshold valuation of fire condition stage 1 in milliamperes (5).
  7. In the Status 2: field set threshold valuation of fire condition stage 2 in milliamperes (6).
  8. In the Short-circuit threshold: field set threshold valuation of the short-circuit in milliamperes (7).
  9. In the Line-break threshold: field set threshold valuation of the line-break in milliamperes (8).
  10. In the Logical AND: field set the number of line that is in the logical dependence with the current line (9).

    Note.

    If 0 value is set then there is no logic connection with the current line.
  11. In order to control exits that are respondent for FIRE CONDITION STAGE I set corresponding Status 1 controlled:  checkboxes (10).
  12. In order to control exits that are respondent for FIRE CONDITION STAGE II set corresponding Status 2 controlled: checkboxes (11).
  13. In order to control relay exits that are respondent for FIRE CONDITION STAGE I set corresponding Status 1 controlled relay: checkboxes (12).
  14. In order to control relay exits that are respondent for FIRE CONDITION STAGE II set corresponding Status 2 controlled relay checkboxes (13).
  15. To save changes click Apply (14).

Configuration of FS5100 panel lines is completed.