For working with the Siemens Cerberus ECO system in the ACFA Intellect PSIM software package it's required to configure it in the vendor software.

...

  1. Login to Siemens Cerberus ECO controller (password is 4321) and switch to Control panel - > Configuring mode.
  2. Connect the Siemens Cerberus ECO devices to the Server.
  3. Run the Siemens Cerberus ECO FXS1800 software (password 4321), create a project and configure a system using official documentation.
  4. Configure a port: type – FMS, baudrate – 115200. These parameters are specified in properties of the External device object based in the tree of the Siemens Cerberus ECO FXS1800 software: Physical tree -> External port -> External device.
  5. Send configuration to controller and save a project.
  6. Rename a project to the cerberus_n.fxc, where n – id of the Siemens Cerberus ECO in the ACFA IntellectPSIM software.
  7. Place the cerberus_n.fxc project file to the <Intellect software installation directory>\Modules folder.
  8. Switch over a controller to the APM mode (Control panel -> APM) and restart it.

...