  1. Go to the Bacnet Provider object settings panel, which is created on the basis of the Bacnet Server object.
  2. From the Type drop-down list (1) select the required type of object in Intellect Axxon PSIM.

  3. From the Object drop-down list (2) select the required object in Intellect Axxon PSIM.

  4. In the Events list (3) set the check boxes for the object events that need to be forwarded.

  5. In the Params list (4) set the check boxes for the parameters that need to be forwarded.

  6. Set the States Forwarding check box (5) if it is necessary to enable the forwarding of the Intellect Axxon PSIM object states.

  7. In the PORT field (6) enter the port within the BACnet network.

  8. In the Max APDU Length Accepted field (7), enter the maximum number of octets (eight binary digits) depending on the type of connection (Bacnet IP, Bacnet MS/TP, etc.).

  9. In the APDU Retries field (8), enter the number of attempts to receive the events and/or parameters from the object in case the request was unsuccessful.

  10. In the APDU Timeout field (9), enter the time interval in milliseconds after which an attempt will be made to re-request if the previous attempt was unsuccessful. Also, this time sets the COV polling period.

    Info
    titleNote

    COV stands for COV Subscriptions, i.e. subscription to BACnet device objects, in this case it is a subscription to the Intellect Axxon PSIM object. The BACnet server waits for the notification about the events and/or Intellect Axxon PSIM object parameter changes in order to forward them.


  11. In the Description field (10), enter the description of the forwarded data, if necessary.
  12. Click the Apply button (11) to save the changes.

...