- Login to Siemens Cerberus ECO controller (password is 4321) and switch to Control panel - > Configuring mode.
- Connect the Siemens Cerberus ECO devices to the Server.
- Run the Siemens Cerberus ECO FXS1800 software (password 4321), create a project and configure a system using official documentation.
- Configure a port: type – FMS, baudrate – 115200. These parameters are specified in properties of the External device object based in the tree of the Siemens Cerberus ECO FXS1800 software: Physical tree -> External port -> External device.
- Send configuration to controller and save a project.
- Rename a project to the cerberus_n.fxc, where n – id of the Siemens Cerberus ECO in the ACFA PSIM software.
- Place the cerberus_n.fxc project file to the <Intellect Axxon PSIM software installation directory>\Modules folder.
- Switch over a controller to the APM mode (Control panel -> APM) and restart it.
...