Note | ||
---|---|---|
| ||
You must register the COM components must be registered on the computer, where the Honeywell Server server is running. To register the COM components, in the <Axxon PSIM installation directory>/Modules folder, run the regsvr32 IPMoudle.dll command with administrator rights and reboot the computer (for details, see the manufacturer's documentation). |
To work with the Honeywellintegration module, you must install and configure the AxACFA feature. For more details, see see Connecting and configuring the AxACFA feature.
...
- Create the Honeywellparent object on the basis of the Axacfa object on the Hardware tab of the System settings window.
In the ip field, specify the IP address of the Honeywell Server server. The default value is 127.0.0.1.
In the Server port field, specify the port number for connecting to the Honeywell Server. The default value is 8888.
In the Honeywell device port field, specify the port number for connecting to the Honeywell device. The default value is 3000.
To apply the connection settings, click the Apply button.
Restart Axxon PSIM if the Honeywell Server server is running locally. If the Honeywell Server server is running remotely, then go to the next step.
To download the configuration, click the Download configuration button. As a result, a tree of objects will be an object tree is built:
Info | ||
---|---|---|
| ||
The created object tree doesn't contain Honeywell zones. You can add them separately on the settings panel of the Honeywell Partition object (see Configuring the partition of the Honeywell integration module). |
The The Honeywell server is also automatically added to the System restart service.
...