To synchronize synchronize and manage the Castle ACS and Intellect ACFA configurations configuration, do the following:

  1. Go to the

    Synchronization parameter group on the

    settings panel of the Castle server object

    (Fig. 3.3 1).

...

  1. .
    Image Added

  2. Set the Use auto synchronization checkbox (1) if it is necessary to send data from the Access Manager module to the Castle server after a specified time period.

  3. In the Password field (2), enter the time period in hours after which the data of the Access Manager module will be sent to the Castle server.

    Info
    titleNote

    The time period count starts from the moment the Castle integration module is launched.


  4. Click the Hardware synchronization button (3) to read the Castle ACS configuration stored on the Castle server and to build the corresponding object tree in the ACFA-Intellect software package.

  5. Set the Dynamic checkbox (4) if it is necessary to automatically send the changed data of the Access Manager module to the Castle server.

    Note
    titleAttention!
    To ensure the proper operation of Castle integration module, it is required that the Dynamic checkbox is always set.


    Info
    titleNote

    In order to speed up the autosync process, the following user sending logic is used.

    The users who have at the time of synchronization:

    • the card issue date, which has not yet come;
    • the card expiration date that has already passed;
    • access levels that are unrelated to the the controllers of this Castle server;
    • or the User locked property

    are not written to the controller.


  6. Click the Send SPR button (5) to send the data from the Access Manager module to the Castle server.

    Note
    titleAttention!

    The Castle server connection to ACFA-Intellect should be configured prior to performing this action.


  7. Click the Send AM data to controllers button (6) to send the previously sent data of the Access Manager module to the Castle controllers.
  8. Click the Apply button (7).

Synchronization and management of Castle ACS configuration are now complete

  1. Parameters are to be auto synchronized between Intellect and Castle servers. Specify the interval for parameters auto synchronization (in hours) in the Synchronization interval field (Fig. 3.3 1, 1).
  2. To read Castle ACS configuration stored on Castle server click the Hardware synchronization button (Fig. 3.3 1, 2).
  3. To send ACFA Intellect configuration to Castle server click the Save configuration button (Fig. 3.3 1, 3).

Important! This action is to be performed after configuring interaction between Intellect and Castle servers.

  1. To clear the Castle server database click the Clear DB button (Fig. 3.3 1, 4).
  2. Click the Apply button.