Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Alarm indicator badges both indicate information and allow performing actions.

  1. Information: If if an alarm occurs, the badge becomes red; if confirmed by the operator, it becomes pink, and when the alarm ends, the badge becomes inactive again.
  2. Actions: The the operator can click the badge to get details on the device or event.

...

To get the details about an alarm, click the alarm's icon. The Reaction to alarm window opens. The title of the window contains the selected object's name and ID.

Image Modified

In the Alarm date field, the time when Server of Control had loaded the alarm from Agent of Control to the database. This is not the time when the alarm appeared on the Agent of Control. For more information on data transmission see section Appendix 1. Data update periods summary.

...

If you check the Confirm box in the Reaction to alarm window, the icon's background in the Control Panel panel changes from red to orange and the Processing date Date of processing column is automatically filled.

Note that the Processing date column Date of processing column will contain not the current computer time, but the current update time (see the Current Update Time section) stored in the database. This ensures that the operator cannot roll back the system time to confirm the alarm with a different time.

...

If when configuring the Monitoring interface  interface object, you check the Non-empty Comment field check box, alarms are not closed until an operator comments on them or his/her actions. Any alarm is closed automatically after its cause is resolved (for example, the connection was broken and then restored).

If a complex confirmation of alarm acceptance is configured, then an additional dialog box appears. To confirm the alarm acceptance click the OK button, to cancel the action click the Cancel button.

Image Modified

Confirmations of alarms that have been automatically accepted by the Server of Control are not sent.

...

The Reaction to alarm window displays no more than 10,000 10000 alarm events; to view other events, use the navigation buttons button Image Added in the lower right corner.Image Removed