To start, configure the StateUPS auxiliary utility.
...
- Address – address of the machine on which Agent of Control is running. The default value of this parameter is 127.0.0.1. If you install StateUPS on the same computer on which Agent of Control is installed, it is not necessary to change this parameter.
- Port – TCP port to which StateUPS sends messages from the UPS. The value of this parameter must match the corresponding setting of Agent of Control, TCP port (UPS) (see the section Configuring a port for incoming UPS messages).
After the
...
StateUPS
...
is configured
...
,
...
install the software from the UPS vendor. Before starting installation, make sure that the interface cable is connected to the UPS.
- To start the installation process, start the executable file pc521.exe in the installation folder UPS\PowerChutePlus. A window opens to inform of the start of installation.
- On the following wizard page, select the option Continue with the installation now and click the Next button.
- On the following wizard page, click the Yes button to accept the license agreement.
- On the following wizard page, select the Typical installation type and indicate the path at which you want to install the software.
- Copying begins of the necessary files.
- When copying is complete, a dialog box appears with a request to automatically determine the COM port on which the UPS is located. Click the Yes button.
- The search process begins.
- When the search is complete, the program will show what type of UPS it found and on which COM port. Click the Next button.
- On the next wizard page, clear the Enable PowerChuteplus remote monitoring check box and click the Next button.
- The two following wizard pages complete the installation process.
Dialog box to confirm installation completion.
Installation of the StateUPS utility is now complete.