Trouble: I cannot create the OnGuard object
Probable cause #1: The object is not added to the intellect.sec license key
Solution #1: Check if the “Intellect ACFA - object OnGuard System” module(s) added to the Axxon Intellect Enterprise license key:
- Locate the intellect.sec license file. It is stored in the Intellect installation directory, usually C:\Program Files (x86)\Intellect\
- Go to https://sale.axxonsoft.com/
- Select Systems – Decoding.
- Drag-and-drop the intellect.sec file to the page.
- Find the “Intellect ACFA - object OnGuard System” string on the page.
- If it is not found, or the number of objects less than you want to create in ACFA Intellect, please contact AxxonSoft sales manager to update the license key.
...
Solution #2: Run ACFA Intellect installation and select OnGuard component in the Combined AC/FA systems group on the Custom Setup stage of the installation process.
Trouble: The “OpenAccess session created successfully” and/or “Events bridge connection established” messages do not appear when I apply the connection settings
Probable cause: The connection between ACFA Intellect and OnGuard cannot be established.
...
- Make sure you run exe with Windows Administrator rights.
- Make sure your firewall does not prevent Intellect core or the integration module from accessing the network.
- Make sure that all necessary ports are properly forwarded in your network (see “Ports used by OnGuard integration module”).
- Try to re-enter credentials in case if there was a typo e.g. in your password. Do not forget to click Apply after the settings change.
Trouble: I cannot read configuration of the OnGuard server or only few of the panels are read
Probable cause #1: The connection between ACFA Intellect and OnGuard was not established.
...
- Locate the intellect.sec license file. It is stored in the Intellect installation directory, usually C:\Program Files (x86)\Intellect\
- Go to https://sale.axxonsoft.com/
- Select Systems – Decoding.
- Drag-and-drop the intellect.sec file to the page.
- Find the «Intellect ACFA - object OnGuard Panel» string on the page.
- If it is not found, or the number of objects less than you want to create in ACFA Intellect, please contact AxxonSoft sales manager to update the license key.
Trouble: There is red “X” icon next to OnGuard object, the module is not working
Probable cause: There was a problem in the module operation.
...
- Go to the AxxonSoft tech support server: https://support.axxonsoft.com/
- Register a new account on the tech support server or sign in to the registered account.
- Create an issue for tech support. Make sure to select “ACFA: ACS/FA OnGuard” component in the creation form.
- Attach the archive generated by Support.exe tool to the created issue.
Please refer here for the details about Support.exe tool.