To configure the BACnet provider, do the following:

  1. Go to

...

  1. the settings panel of the Bacnet Provider object

...

  1. that is created on the basis of the Bacnet Server object.
    Image Modified
  2. From the Type drop-down list

...

  1. , select the required type of object in Axxon PSIM.

  2. From the Object drop-down list

...

  1. , select the required object in Axxon PSIM.

...

In the Events list (3) set the check boxes for the object events that need to be forwarded.

...

In the Params list (4) set the check boxes for the parameters that need to be forwarded.

  1. Set the States Forwarding

...

  1. checkbox to forward the states of an object to Axxon PSIM.
  2. In the PORT field

...

  1. , enter the port within the BACnet network.

  2. In the Max APDU Length Accepted

...

  1. field, enter the maximum number of octets (eight binary digits) depending on the type of connection (Bacnet IP, Bacnet MS/TP,

...

  1. and so on).

  2. In the APDU Retries

...

  1. field, enter the number of attempts to receive the events and/or parameters from

...

  1. an object in case the request was unsuccessful.

  2. In the APDU Timeout

...

  1. field, enter the time interval in milliseconds, after which an attempt will be made to re-request if the previous attempt was unsuccessful. Also, this time

...

  1. specifies the COV polling period.

    Info
    titleNote

    COV

...

  1. is COV Subscriptions,

...

  1. that is, subscription to objects of the BACnet device

...

  1. , in this case, it is a subscription to the Axxon PSIM object. The BACnet server waits for the notification about the events and/or Axxon PSIM object parameter changes in order to forward them.

  2. In the Description field

...

  1. , enter the description of the forwarded data, if necessary.
  2. Click the Apply

...

  1. button to save the changes.

The BACnet provider configuration is now complete.