  1. Go to the MicroTrack II Segment object’s settings panel.
  2. In the Beginning field (1) using the up-down buttons enter the number of subcell corresponding to the key point in which the control segment started.
  3. In the End field (2) using the up-down buttons enter the number of subcell corresponding to the key point in which the control segment finished.

    Info
    titleNote.
    The range of values of Beginning and End fields is from 0 to 215. It is not recommended for the control segments to overlap one another.


    Note
    titleAttention!
    Value in the End field should not exceed the value in the Beginning field.


  4. In the Timeout field (3) set the interval, after which the alarm will be activated.
  5. In the Control AIM field (4) select an AIM security detector alarm input of the AIM II controller, which the trigger the alarm at a given interval.
  6. In the Alarm fix cause table (5) specify up to 10 alarm descriptions, one of which can be selected by an operator when processing the alarm of a MicroTrack II segment on the map (see Managing MicroTrack II and MicroPoint II control segments).
  7. Click Apply button (6).

...