Go to documentation repository
Previous page Next page
To configure the AR-721 controller, do the following:
- Go to the AR-721 object's settings panel.
- From the Region In drop-down list select the Area located in the site of entry through this reader (1).
- From the Region Out drop-down list select the Area located in the site of exit through this reader (2).
From the Mode drop-down list select the required mode of the controller (3). The list of available modes is given in the table.
Mode
Networking/ Stand-Alone
User Capacity
Access Mode
Auto-show Duty time
Event log Capacity
120 Holidays
Anti force
Time Zone
Lift Control
Anti-pass-back
M4
Networking/ Stand-Alone
1,024/3,000 (725H)
1.Card only.
2.Card and PIN (4-digit PIN) + #.
3.Card or User address (5-digit) + Individual PIN (4-digit individual PIN) + #.
Yes
1200/1500 (725H)/3000 (757H)
Yes
Yes
11
32
Yes
M6
Stand-Alone
65,535
1. Card only.
2. Card and PIN (4-digit public PIN=Arming PWD) + #.
3. Card or PIN (4-digit public PIN=Duress code).
No
No
No
No
No
No
No
M8
Networking/ Stand-Alone
1,024/3,000 (725H)
1.Card only.
2.Card and PIN (4-digit individual PIN) + #.
3.Card or PIN (4-digit individual PIN).
Yes
1200/1500 (725H)/3000 (757H)
Yes
Yes
11
32
Yes
Attention!
The connection between the AR-721 controller and the ACFA Intellect software will not be established while the M6 mode selected.
- Click Set up Time Zones to configure the matching between time zones of device and time zones of Intellect Server (4) .
- In the Intellect TZ column select the time zone in ACFA Intellect corresponding to the time zone of Soyal device (1).
- Click OK to confirm changes (2).
- In the Intellect TZ column select the time zone in ACFA Intellect corresponding to the time zone of Soyal device (1).
- In the Duress password field enter the code which is using when the computer opens door and at the same time sends a message for help (5).
- In the Master password field enter the code which allows programming device (6).
- In the Arming password field enter the code for arming (7).
- In the Base configuration section enter the time of relay activation and delay time (4).
- In the Extended option sections select the needed function settings checkboxes (5). Descriptions of all options see in the vendor documentation.
- Click the Apply button.
Configuring parameters of the AR-721 controller is completed.