AIM reader is configured on the settings panel of the Apollo AIM reader object created on the basis of the Apollo AIM object.
To configure AIM module, do the following:
From the Access request mode drop-down list, select responsible part for decision of access: the Intellect Server (automatic decision based on user access level and its card) or operator (4).
For processing request by operator it's required to create the Event Manager interface object and configure it for the Operator request (Access granted) event. For detailed information about this object and its functionality see Event Manager Module Settings and Operation Guide. |
From the Initial drop-down list, select the mode of reader operation while connection establishing (5).
Operation mode | Description |
---|---|
Closed | Access is closed for all |
Card only | Access granted by access card |
PIN or card | Access granted by access card or PIN code |
Card and PIN | Access granted by access card and PIN code |
Opened | Access is opened for all |
Facility code | Access is granted by facility code |
The SDK ID (9) field is filled in automatically while object creating and it contains different values for objects of the same type. It's not recommended to create objects by template (see The Save function) for correct working of module because of equal SDK ID values. |
Specify other parameters of reader.
Parameter | Parameter setting method | Description |
---|---|---|
Time of door closing, s | Enter the value in the field | Time of opening in seconds |
Time of door holding, s | Enter the value in the field | Time period in seconds during which door is to be closed. Otherwise, the Door holding message will be triggered |
Alternative time of door closing, s | Enter the value in the field | Alternative time of opening in seconds. It is in use by special command (from card, using macro or script) |
Alternative time of door holding, s | Enter the value in the field | Alternative time period in seconds during which door is to be closed. Otherwise, the Door holding message will be triggered. It is in use by special command (from card, using macro or script) |
Allow impulse reset | Set the checkbox | Yes — impulse reset enabled |
Do not use full time of door closing | Set the checkbox | Yes — lock after door closing |
Do not use exit button | Set the checkbox | Yes — disable exit button |
Use AUX as sensor of door opening | Set the checkbox | Yes — use additional AUX sensor of AIM module as sensor for door opening |
Do not wait for access cycle | Set the checkbox | Yes — passage is performed after making an access decision No — passage is performed after triggering a sensor of door opening |
Use "soft" APB | Set the checkbox | Yes — antipassback is available, but the corresponding mistake will be specified in message |
Forbid duress entrance | Set the checkbox | Yes — door is locked while entering "duress" PIN-code No — door is opened and alarm message is triggered while entering "duress" PIN-code |
Access request if access is allowed by hardware | Set the checkbox | Yes — send access request to operator if AIM or AAN allow access |
Access request if access is forbidden by hardware | Set the checkbox | Yes — send access request to operator if AIM or AAN forbid access |
Load configuration to reader | Set the checkbox | Yes — duplicate users and their access levels to the memory of AIM module while writing of configuration to the AAN controller |
Make decision on access locally | Set the checkbox | Yes — the AIM module makes an access decision without the AAN central controller |
Warning before alarm | Set the checkbox | Yes — trigger warning before alarm |
Entrance by two cards | Set the checkbox | Yes — passage through the reader is performed by two cards |
Sound notification while door unblocking | Set the checkbox | Yes — sound signal of reader while unblocking the door |
Disable second door in binding mode | Set the checkbox | Yes — block the reader working for exit from secured areas |
Disable only bounded reader while blocking | Set the checkbox | Yes — only bounded reader are blocked while locking signal No — all readers are blocked |
Use cards buffering while passage | Set the checkbox | Yes — write access cards to the AIM while passage |
Limit of PIN code fitting | Select the value from the list | Lock is blocked while exceeding of invalid PIN-code entrances |
Delay of timed APB, min | Select the value from the list | Time interval in minutes during which antipassback is forbidden |
Mode of additional relay | Select the value from the list | Connection with alarms — additional relay is triggered while alarm Manual control — additional relay is activated manually |
IV Settings | Click the button | See Associating AIM reader commands with terms |
The AIM reader is now configured.