The AIO relay is configured on the settings panel of the Apollo AIO Relay object created on the basis of the Apollo AIO object.
The AIO relay is configured as follows:
From the Mode: drop-down list select the mode of relay working (2).
Mode of relay working | Description |
---|---|
Disabled | Relay opened |
Enabled | Relay closed |
Connected with inputs locally | State of relay depends on state of loops and inputs |
Configure interaction of relay and inputs (12). In the Type of connection column select state of input at which relay will be closed.
State | Description |
---|---|
Not connected | Relay is always opened at any state of input |
Alarm and tamper | Relay is triggered in one of the following ways: a. Alarm message from input was received. b. Message from tamper was received. |
Alarm/masked and tamper | Relay is triggered in one of the following ways: a. Alarm message from input was received. b. Alarm message from disarmed input was received. c. Message from tamper was received. |
Alarm/masked, tamper and failure | Relay is triggered in one of the following ways: a. Alarm message from input was received. b. Alarm message from disarmed input was received. c. Message from tamper was received. d. Message about failure was received. |
The AIO relay is now configured.