The controller C3-100 is configured on the settings panel of the AC ZK Controller C3-100 object which is created on the basis of the AC ZK Teco object on the Hardware tab of the System settings dialog window.
To configure the C3-100 controller, do the following:
From the Anti-passback: drop-down list select the mode of anti-passback operation (4):
Mode | Description | Controller |
---|---|---|
Disable | The anti-passback function is disabled | All controllers |
Readers of Door 1 | The anti-passback function is enabled between the readers of Door 1 | ZK C3-100, ZK C3-200 |
Readers of Door 2 | The anti-passback function is enabled between the readers of Door 2 | ZK C3-200 |
Readers of door 1, readers of door 2 | The anti-passback function is enabled between the readers of Door 1 and Door 2 respectively | ZK C3-200 |
Door 1 and 2 | The anti-passback function is enabled between the readers of Door 1 and Door 2 | ZK C3-200, ZK C3-400 |
Doors 3 and 4 | The anti-passback function is enabled between the readers of Door 3 and Door 4 | ZK C3-400 |
Doors 1 and 2, doors 3 and 4 | The anti-passback function is enabled between the readers of Door 1, Door 2, Door 3 and Door 4 | ZK C3-400 |
Doors 1, 2 and doors 3, 4 | The anti-passback is enabled between Door 1, 2 and Door 3, 4 | ZK C3-400 |
Door 1 and doors 2, 3 | The anti-passback is enabled between Door 1 and Door 2, 3 | ZK C3-400 |
Door 1 and doors 2, 3, 4 | The anti-passback is enabled between Door 1 and Door 2, 3, 4 | ZK C3-400 |
From the Interlock: drop-down list select the mode of doors interlocking (5):
Mode | Description | Controller |
---|---|---|
Disable | The interlock function is disabled | All controllers |
Door 1 and 2 | Doors 1 and 2 are interlocked mutually | ZK C3-200, ZK C3-400 |
Door 3 and 4 | Door 3 and door 4 are interlocked mutually | ZK C3-400 |
Doors 1, 2 and 4 | Door 1, door 2 and door 4 are interlocked mutually | ZK C3-400 |
Doors 1 and 2, doors 3 and 4 | Door 1 and door 2 are interlocked mutually, door 3 and door 4 are interlocked mutually | ZK C3-400 |
Doors 1, 2, 3 and 4 | Door 1, door 2, door 3 and door 4 are interlocked mutually | ZK C3-400 |
Set the Watch dog checkbox to activate the control mode (7).
The version of firmware and serial number of controller will automatically display in the corresponding fields while connecting the controller (8). |
Configuring of the C3-100 controller is completed.