The Cerberus PRO panel connection is configured as follows:

  1. Create the CerberusPRO Panel object on the basis of the Computer object on the Hardware tab of the System Settings dialog box.

  2. In the Panel IP address field (1) specify the IP address of the Cerberus PRO panel.
  3. In the UDP port field (2) specify the UDP port of the Cerberus PRO panel.
  4. In the BACnet device ID field (3) specify the BACnet server identifier (see Configuring the BACnet server Cerberus PRO).
  5. In the Timeout (ms) field (4) specify in milliseconds the timeout for reading the parameters of the Cerberus PRO panel.
  6. In the Retries field (5) specify the number of connection retries.
  7. To read the configuration from the Cerberus PRO panel, click on the Read configuration from panel button (6). As a result, child objects corresponding to the panel configuration will be created.

    Set the Do not update names checkbox (7) to prevent overwritten object names when re-reading the configuration from the panel.

    If the connection is successful, information about the connected panel will be displayed in the Object name and Description fields (8).

  8. Click the Apply button (9) to save settings.