 The configuration of FS5200 panel is carried out on the setting panel of the FS5200 panel object. This object is created on the basis of the UniPos 4000/5000 FSA object on the Hardware tab of the System settings dialog box while constructing the UniPos object tree (see Construction of the UniPos 4000/5000 FSA object tree).

Configuration of FS5200 panel is carried out the following way:

  1. Go to the setting panel of the FS5200 panel object.

    Note.

    In the Type field the name of FS5200 panel is displayed (1).

    Note.

    In the Number field the id of FS5100 panel is displayed (2).
  2. With the help of up-down buttons in the Recognition time field set the transition time from FIRE CONDITION STAGE I to FIRE CONDITION STAGE II (in seconds) ( 3).
  3. In the Time constant: field set time correction value for keeping rate of built-in clock in case of exceeding or laggging from astronomical time. Correction value possesses the value from -63 to 63 (4).
  4. To save changes click Apply (5).

Configuration of FS5200 panel is completed.