Documentation for ACFA PSIM 1.3.

Previous page Configuring AAN controller  Configuring AAN, AIO and AIM Service input Next page

AIM module and AIO security panel are connected to the AAN controller via four ports (RS-485 or Ethernet).

Port is configured on the settings panel of the Apollo AAN Port object created on the basis of the Apollo AAN object.

To configure port of the AAN controller, do the following:

Attention!

It is not recommended to change default port parameters.

  1. From the Mode drop-down list (1), select the mode of data exchange: duplex or half duplex. Duplex mode receives and sends data simultaneously. Receiving and sending data in half duplex mode are performed in interval.
  2. In the Transmission delay, ms field (2), specify the delay of data exchange via port in milliseconds.
  3. In the Delay before reception, ms field (3), specify the delay before data reception via port in milliseconds. 
  4. In the Max. time between bytes, 10 ms field (4), specify the maximum time of waiting for the next byte in milliseconds.

    Note

    Names of this and the next parameter contain multiplicity of value which must be specified. So, if it's required to specify value of the Max. time between bytes, 10ms equal to 4, then maximum time of waiting for the next byte will be 40 ms.

  5. In the Response time, 10 ms field (5), specify the maximum time of response from devices connected via this port, considering the specified multiplicity. If device does not response during the specified time, connection with it is lost.
  6. In the Period of polling, 25 ms field (6), specify in miliseconds the period of polling of devices connected via this port if there is connection with them, considering the specified multiplicity.
  7. In the Period of polling while loss of connection, 25 ms field (7), specify in miliseconds the period of polling of devices connected via this port if there is no connection with them, considering the specified multiplicity.
  8. Click the Apply button.
  • No labels