The Virdi output is configured as follows:
- Go to the settings panel of the Virdi Output object that is created on the basis of the Virdi ACU object.
- From the PGM number drop-down list, select the output number from 1 to 8.
- From the PGM type drop-down list, select the output type:
- Unused—not used.
- Matching success—triggers after successful authorization of a user.
- Matching failed—triggers after an unsuccessful authorization of a user.
- Scheduled output—works according to the assigned schedule.
- Alarm output—triggers when an alarm is activated.
- System troubles—triggers when a problem occurs in the system, for example, a problem with the battery, a problem with the reader, and so on.
- Arm/disarm status—triggers when a region becomes armed/disarmed.
- Fire alarm—triggers when a fire alarm is activated.
- Silent alarm—triggers when a silent alarm is activated.
- Open too long—triggers when the door is open for too long.
- Door forced—triggers when the door is held by force.
- In the Param (dep. on type) drop-down list:
- if the Matching success or Matching failed output type is selected, then select the door number that will be opened when the corresponding output is triggered: from 1 to 4.
- if the Alarm output, Fire alarm, or Silent alarm output type is selected, then select the section number in which the alarm will be triggered when the corresponding output is triggered: from 1 to 4.
- if the Scheduled output output type is selected, then select the schedule number according to which the corresponding output will operate: from 0 to 255.
- From the Activation time drop-down list, select the time in seconds for which the output will be activated: from 0 to 255.
- Set the Inverted output checkbox if it is necessary to invert the output.
- Click the Apply button to apply the settings.