For working with the Siemens Cerberus ECO system in the ACFA Intellect software package it's required to configure it in the vendor software.
The Siemens Cerberus ECO FXS1800 software is provided with devices.
Siemens Cerberus ECO system is configured as follows:
- Login to Siemens Cerberus ECO controller (password is 4321) and switch to Control panel - > Configuring mode.
- Connect the Siemens Cerberus ECO devices to the Server.
- Run the Siemens Cerberus ECO FXS1800 software (password 4321), create a project and configure a system using official documentation.
- Configure a port: type – FMS, baudrate – 115200. These parameters are specified in properties of the External device object based in the tree of the Siemens Cerberus ECO FXS1800 software: Physical tree -> External port -> External device.
- Send configuration to controller and save a project.
- Rename a project to the cerberus_n.fxc, where n – id of the Siemens Cerberus ECO in the ACFA Intellect software.
- Place the cerberus_n.fxc project file to the <Intellect software installation directory>\Modules folder.
- Switch over a controller to the APM mode (Control panel -> APM) and restart it.
Note.
Switching over to the APM mode is forbidden in old versions of controller firmware. Contact the vendor to get the current version of firmware and information about its installation.
Configuring of the Siemens Cerberus ECO system is completed.