Documentation for Monitoring PSIM 1.0 (english)

Previous page Settings panel of the Partition Of Control object  Settings panel of the Monitoring interface object Next page

Settings panel of the Server Of Control object is given on figure.

Description of the Server Of Control object settings panel elements is given in table.

#

Name

Method for setting the parameter value

Description

Type

Default value

Value range

1

Identifier

Automatically

Shows the identification number of the Server Of Control object in the system

Nonnegative integer

-

>=0

2

Name

Enter the value in the field

Shows the name of the Server Of Control object in the system

Latin letters and service characters

Server Of Control

A line representing a sequence of any symbols (letters, digits, service characters apart from > and < symbols), not case-sensitive.
Number of symbols – from 1 to 60

3

Computer

Is selected in the list

Assigns the parent Computer object for the Server Of Control object

Name of the Computer objects registered in the system. 

Name of the parent Computer object

Depends on the number of the Computer objects in the system

4IIDK interface

Enter a value in the field

Sets the ID of the IIDK interface object used by the Server of Control

Nonnegative integer150>=0
5Event Viewer

Click the button


Opens the Event Viewer tool 

---

Advanced group

6

Monitoring…

Click the buttonOpens the box of setting the list of additional workplaces


7

Snapshots/video...

Click the button

Opens a dialog box for configuring reaction to snapshots and videos receiving on sensors alarms at the Agent of Control

-

-

-

Logging subsystem group

8

Auxiliary characters

Is set in a checkbox

Enables logging of auxiliary characters at the transport level into the event log

Boolean

False

True – logging of auxiliary characters is enabled
False – logging of auxiliary characters is not performed

9

Alarm events

Is set in a checkbox

Enables logging alarms into the event log

Boolean

True

True – logging of alarms is enabled
False – logging of alarms is not performed

10

System status

Is set in a checkbox

Enables logging of events related to system status

Boolean

True

True – logging of events related to system status is enabled
False – logging of events related to system status is not performed

11

Archive period (h)

Enter the value in the field

Sets the frequency at which the log file is to be archived

Hours

48

>0

12

File size (MB)

Enter the value in the field

Sets the file size threshold upon which the log file is archived. This setting overrides the value in the Archive period (h) field

Megabytes

100

>0

13

Keep archives for (months)

Enter the value in the field

Sets the length of time for which you want to store archived log files

Months

3

from 1 to 24

Transfer group

14

TCP/IP port (Agent)

Enter the value in the field

Sets the port number for TCP/IP communication with remote objects of Agent Of Control

Nonnegative integer

7777

from 1 to 60000

15

TCP/IP port (Archive)

Enter the value in the field

Sets the port number for TCP/IP communication with remote Search in archive module

Nonnegative integer

7755

from 1 to 60000

16

First COM port number

Is selected in the list

Sets the first COM port number

COM-ports names

Com1

from Com1 to Com 256

17

Number of COM ports

Is selected in the list

Sets number of COM ports used

Nonnegative integer

1

from 1 to 256

18

COM port speed

Is selected in the list

Sets the COM port speed

Baud

9600

110
300
1200
2400
4800
9600
19200
38400
57600

19

COM port format

Enter the value in the field

Sets the COM port format

COM port format

8N1

  • first digit: from 5 to 9 data bits
  • second letter: N (No parity) – no parity bit, E (Even parity) - even parity bit, O (Odd parity) – odd parity bit
  • third digit: 1 or 2 stop bits

Outside the groups

20

Transfer info about confirmed alarms to Agent Of Control

Set the checkbox

Enables sending confirmations of alarm acceptance by the operator on the Server of Control to the Agent of Control

Boolean type

Yes

True – confirmations of alarm acceptance are sent

False – confirmations of alarm acceptance are not sent

21

Restart

Click the button

VideoSrv communication module restarting

-

-

-