To configure AIM module, do the following:

Image Modified

  1. From the Number: drop-down list, select the reader address (1).
  2. From the Entrance to: drop-down list, select the Region object corresponding to the area on the side of exit through this reader (2).
  3. From the Exit from: drop-down list, select the Region object correcponding corresponding to the area on the side of entrance throught through this reader (3).
  4. From the Access request :mode drop-down list, select responsible part for decision of access: the Intellect Server (automatic desicion based decision based on user access level and its card) or operator (4). 

    Info
    titleNote.

    For processing request by operator it's required to create the Event Manager interface object and configure it for the Operator request (Access granted) event. Fot For detailed information about this object and its functionality see the Event Manager Module Settings and Operation Guide.


  5. Configure operation modes of reader:
    1. From the Initial: drop-down list, select the mode of reader operation while connection establishing (5).

      Operation modeDescription
      ClosedAccess is closed for all
      Card onlyAccess granted by access card
      PIN or cardAccess granted by access card or PIN code
      Card and PINAccess granted by access card and PIN code
      OpenedAccess is opened for all
      Facility codeAccess is granted by facility code


    2. From the Independent: drop-down list, select the mode of reader operation while losing of connection (6).
    3. Set the Use initial codemode checkbox, if it's required to swich switch to initial mode after writing of configuration (7).
    4. Click the Modes by time zones button and configure changing of reader operation mode depending on time zone (8). Two operation modes are selected for each time zone: at the start of time zone and after end of time zone.
    Info
    titleNote.

    The SDK ID (9) field is filled in automatically while object creating and it contains different values for objects of the same type. It's not recommended to create objects by template (see The Save function) for correct working of module because of equal SDK ID values.


  6. Specify other parameters of reader.

    ParameterParameter setting methodDescription
    Time of door closing, sEnter the value in the fieldTime of opening in seconds
    Time of door holding, sEnter the value in the fieldTime period in seconds during which door is to be closed. Otherwise, the Door holding message will be triggered
    Alternative time of door closing, sEnter the value in the fieldAlternative time of opening in seconds. It is in use by special command (from card, using macro or script)
    Alternative time of door holding, sEnter the value in the fieldAlternative time period in seconds during which door is to be closed. Otherwise, the Door holding message will be triggered. It is in use by special command (from card, using macro or script)
    Allow impulse resetSet the checkboxYes
    impulse reset enabled
    Do not use full time of door closingSet the checkboxYes
    lock after door closing
    Do not use exit buttonSet the checkboxYes
    disable exit button
    Use AUX as sensor of door openingSet the checkboxYes
    use additional AUX sensor of AIM module as sensor for door opening
    Do not wait for access cycleSet the checkbox

    Yes

    passage is performed after making an access decision

    No

    passage is performed after triggering a sensor of door opening

    Use "soft" APBSet the checkboxYes antipassback is available, but the corresponding mistake will be specified in message
    Forbid duress entranceSet the checkbox

    Yes

    door is locked while entering "duress" PIN-code

    No

    door is opened and alarm message is triggered while entering "duress" PIN-code

    Access request if access is allowed by hardwareSet the checkboxYes
    send access request to operator if AIM or AAN allow access
    Access request if access is forbidden by hardwareSet the checkboxYes
    – send
     send access request to operator if AIM or AAN forbid access
    Load configuration to readerSet the checkboxYes
    duplicate users and their access levels to the memory of AIM module while writing of configuration to the AAN controller
    Make decision on access locallySet the checkboxYes
    the AIM module makes an access decision without the AAN central controller
    Warning before alarmSet the checkboxYes
    trigger warning before alarm
    Entrance by two cardsSet the checkboxYes
    passage through the reader is performed by two cards
    Sound notification while door unblockingSet the checkboxYes
    sound signal of reader while unblocking the door
    Disable second door in binding modeSet the checkboxYes
    block the reader working for exit from secured
    ares
    areas
    Disable only bounded reader while blockingSet the checkbox

    Yes

    only bounded reader are blocked while locking signal

    No

    all readers are blocked

    Use
    "soft" APBSet the checkboxYes – antipassback is available, but the corresponding mistake will be specified in mesageUse
    cards buffering while passageSet the checkboxYes
    write access cards to the AIM while passage
    Limit of PIN code fittingSelect the value from the listLock is blocked while exceeding of invalid PIN-code entrances
    Delay of
    temporary
    timed APB, minSelect the value from the listTime interval in minutes during which antipassback is forbidden
    Mode of additional relaySelect the value from the list

    Connection with alarms

    – additional

    — additional relay is triggered while alarm

    Manual control

    – additional

    — additional relay is activated

    manualy

    manually

    IV SettingsClick the buttonSee Associating AIM reader commands with terms
    .


  7. Click the Apply (9) button.

The AIM reader is now configured.