Go to documentation repository
Previous page Next page
To synchronize Castle ACS and Intellect ACFA configurations do the following:
Go to the Synchronization parameter group on the settings panel of the Castle server object.
Set the Use auto synchronization checkbox to automatically synchronize parameters between Intellect Server and Castle Server (1).
Attention!
The Use auto synchronization checkbox is always to be checked for proper operation of Castle integration module.
In the Synchronization interval, h field, set the period (in hours) of parameters synchronization (2).
To read Castle ACS configuration stored on Castle server click the Hardware synchronization button (3).
To send ACFA Intellect configuration to Castle server click the Save configuration button (4).
Attention!
This action is to be performed after configuring interaction between Intellect and Castle servers.
Set the Dynamic sending checkbox to enable constant connection between Intellect and Castle servers (5).
Attention!
The Dynamic sending checkbox is always to be checked for proper operation of Castle integration module. If it is not, use Save configuration or Send AM data to controllers every time you change hardware or user parameters correspondingly.
Click Send AM data to controllers to send configuration of ACFA Intellect users to Castle controllers (6).
Set the Transmit command to record to controllers checkbox to enable automatic sending of ACFA Intellect users configuration to controllers after clicking Save configuration (7).
Note.
If the Transmit command to record to controllers checkbox is not set, click Send AM data to controllers (6) every time after clicking Save configuration (4).
- Click the Apply button.
Note
In order to speed up the autosync process, the following user sending logic is used.
The users who have at the time of synchronization:
1. the card issue date, which has not yet arrived;
2. the card expiration date that has already passed;
3. access levels that are unrelated to the the controllers of this Castle server;
4. or the User locked property
are not written to the controller.
Castle ACS and Intellect ACFA configurations are now synchronized.