Tables
Designations

The following designations are in the reference guide:

(x32) - HKEY_LOCAL_MACHINE\SOFTWARE\ITV\INTELLECT\ registry section

(x64) - HKEY_LOCAL_MACHINE\SOFTWARE\Wow6432Node\ITV\INTELLECT registry section

For the ATM-Intellect software:

(x32-ATM/Monitoring) – HKEY_LOCAL_MACHINE\SOFTWARE\BitSoft\VHOST\VHostService registry section

(x64-ATM/Monitoring) – HKEY_LOCAL_MACHINE\SOFTWARE\Wow6432Node\BitSoft\VHOST\VHostService registry section

For the ATM Event Capture utility:

(x32-ATM Event Capture) – HKEY_LOCAL_MACHINE\SOFTWARE\ITV\EventATM registry section

(x64-ATM Event Capture) – HKEY_LOCAL_MACHINE\SOFTWARE\Wow6432Node\ITV\EventATM registry section

 

 

General information on Windows OS registry and working with it is given in the Working with Windows OS registry section of the Administrator's Guide.


ACFA Intellect

Registry section

String parameter

Available values

Default

Product version

Parameter in effect

Rovalant A6-A16 ISS 

 

 

 

 

 

x32: (x32)\Rovalant_A6_A16
x64: (x64)\Rovalant_A6_A16

access_point_count

-

10

4.7.6 and later

Internal module setting. You’d better not modify the key.

x32: (x32)\Rovalant_A6_A16
x64: (x64)\Rovalant_A6_A16

rele_count

-

20

4.7.6 and later

Internal module setting. You’d better not modify the key. 

Apollo (AAN 100, AAN 32, AIM-4, AIM-4SL)

 

 

 

 

 

x32: (x32)\Apollo
x64: (x64)\Apollo

DisableLogOffLineEvents

0, 1

0

4.7.4 and later

Disables event logging when the controller is in the offline mode.

x32: (x32)\Apollo
x64: (x64)\Apollo

EnableHardwareReset

0, 1

1

4.7.4 and later

Enables hardware reset before forwarding configuration.

x32: (x32)\Apollo
x64: (x64)\Apollo

nCardType

0, 1

0

4.7.4 and later

Defines the card type. When the value is 1, support for Weigand32 is enabled.

x32: (x32)\Apollo
x64: (x64)\Apollo

nPINType

0, 1, 2

1

4.7.4 and later

Defines whether PIN is in use:
0 – not is use;
1- PIN 4 figures;
2 - PIN 6 figures.

x32: (x32)\Apollo
x64: (x64)\Apollo

SetLinkParametersAfterReset

0, 1

1

4.7.4 and later

Sets link parameters after reset.

ABC (Access Net) 

 

 

 

 

 

x32: (x32)\ABC
x64: (x64)\ABC

UseDynamic

0, 1

0

4.7.4 and later

Defines whether the Dynamic checkbox is available in the controller settings. In this case configuration forwarding in a separate stream can cause module crash.

x32: (x32)\ABC
x64: (x64)\ABC

UseMultiThreaded

0, 1

0

4.7.4 and later

Sets the use of the multithreading mode.

Perco Card Reader

 

 

 

 

 

x32: (x32)\Perco CR
x64: (x64)\Perco CR

ReadTotalTimeoutConstant

> = 0

-

4.7.4 and later

Sets timeout of reader query. If connection is lost sometimes, then the value is to be increased.

PERCO-SYSTEM-12000L ACS 

 

 

 

 

 

x32: (x32)\Perco
x64: (x64)\Perco

AdditionNumberOfCard

 

0

4.7.4 and later

If the number of card is read with displacement (error of COM Server Perco), then the value of this parameter defines the displacement.

x32: (x32)\Perco
x64: (x64)\Perco

AutoconfigType

0, 1,2,3

0

4.7.5 and later

Sets auto configuration mode:
0 – feature is not available;
1 – controllers that do not exist are deleted;
2  - controllers that do not exist are deleted and new found controllers are stored at the end of the object tree;
3 – new found controllers are stored at the end of the object tree.

x32: (x32)\Perco
x64: (x64)\Perco

DisableOffLine

0, 1, 2

0

4.7.4 and later

0  - standard action;
1 - controller access  to all cards with  shift schedule is forbidden;
2 - controller access to all cards is forbidden.

x32: (x32)\Perco
x64: (x64)\Perco

RequestTime

> = 0

1000

4.7.4 and later

Sets the time period during which the log is read, at the end of this period the reading stops and commands are executed (ms).

x32: (x32)\Perco
x64: (x64)\Perco

SendLevelBeforePerson

0, 1

0

4.7.4 and later

Defines whether to send the access level after sending person to controller or not.

x32: (x32)\Perco
x64: (x64)\Perco

ShowSendLevel

0, 1

0

4.7.4 and later

Defines whether the Send access levels button is shown for Perco object in Intellect settings or not:
0 - disabled (by default);
1 – enabled.

x32: (x32)\Perco
x64: (x64)\Perco

Show_progress

0, 1

0

4.7.4 and later

Defines whether to show progress bar when forwarding configuration or not.

x32: (x32)\Perco
x64: (x64)\Perco

TimeOut

-

-

4.7.4 and later

Set the gateway query timeout.

x32: (x32)\Perco
x64: (x64)\Perco

VerifyLogMesDB

-

-

-

The key is not in use.

Rubeg

 

 

 

 

 

x32: (x32)\RUBEG8_ISB
x64: (x64)\RUBEG8_ISB

ConvertUserBcpToUserIntellect

0, 1

0

4.7.4 and later

Defines whether to allow Rubeg users to access Intellect or not:
0 - forbid importing Rubeg users to Intellect;
1 - allow importing Rubeg users to Intellect.

x32: (x32)\RUBEG8_ISB
x64: (x64)\RUBEG8_ISB

ShowError

0, 1

0

4.7.4 and later

Defines whether to show dialog boxes with Rubeg COM server errors:
0  - forbid displaying dialog boxes;
1 - allow displaying dialog boxes.

x32: (x32)\RUBEG8_ISB
x64: (x64)\RUBEG8_ISB

UseThreadDynamicProcess

0, 1

1

4.7.5 and later

Sets the thread for forwarding user configuration:
0 - forwarding in the primary thread;
1 - forwarding in the secondary thread.

x32: (x32)\RUBEG8_ISB
x64: (x64)\RUBEG8_ISB

UseCorrectDuplicateUsers0, 104.7.6 and later

1 - algorithm of correction of duplicated users is in use;
0 - algorithm of correction of duplicated users is not in use.

x32: (x32)\RUBEG8_ISB
x64: (x64)\RUBEG8_ISB

UseConfigurationManager0, 10ACFA 6.1

The key is required for operation of integration with Failover module.

0 – do not save Rubezh server configuration to DB.

1 – save Rubezh server configuration to DB.

If Rubezh server configuration is not saved to DB, then it is stored in rcf files. When moving configuration to backup server these files will stay at dead computer and become unavailable, i.e. all settings will be reset to their defaults.

NAC-501/W6500.CNT ACS controller

 

 

 

 

 

x32: (x32)\Nac\Dll
x64: (x64)\Nac\Dll

delay

> = 1

1

4.7.4 and later

Delay (ms) when sending users between them. Default - 1 (no delay).

x32: (x32)\Nac
x64: (x64)\Nac

Delay green led

> = 0

0

4.7.4 and later

Defines how much time (ms) the reader (NAC51P only) is excluded from the query after receiving the event.

x32: (x32)\Nac
x64: (x64)\Nac

Delay open door

> = 0

500

4.7.4 and later

Defines how much time (ms) the reader (NAC51P only) is excluded from the query after authorized access.

x32: (x32)\Nac
x64: (x64)\Nac

Delay prohibited access

> = 0

250

4.7.4 and later

Defines how much time (ms) the reader (NAC51P only) is excluded from the query after enabling the prohibited access mode.

x32: (x32)\Nac
x64: (x64)\Nac

Delay red led

> = 0

250

4.7.4 and later

Defines how much time (ms) the reader (NAC51P only) is excluded from the query after prohibiting access.

x32: (x32)\Nac
x64: (x64)\Nac

enable_thread

1

1

4.7.4 and later

Checkbox of forwarding configuration in a separate thread; the value is always 1 (do not modify). The key is out of date.

x32: (x32)\Nac
x64: (x64)\Nac

fqLinkSet

> = 0

1000

4.7.4 and later

Defines the rate (ms) of attempts to connect the reader if there is no connection.

x32: (x32)\Nac
x64: (x64)\Nac

FlagsLog

0x01 - erroneous file recording/reading
0x02 - sent commands
0x04 - poll
0x08 - erroneous answers to sent commands
0x10 - erroneous answers to poll commands
0x20 - the reader is occupied, repeat is in nn ms
0x40 - card status confirmation
0x80 - master card is shown
0x100 - door open/close
0x200 - TIMEOUT

0x02F9

4.7.4 and later

Sets bit values for logging to log file (what to log).

x32: (x32)\Nac\Dll
x64: (x64)\Nac\Dll

show_progress

0, 1

1

4.7.4 and later

Defines whether to show the progress when forwarding the configuration.

SATEL FAS ACS

 

 

 

 

 

x32: (x32)\Satel
x64: (x64)\Satel

Get_Outputs

0, 1

1

4.7.4 and later

1 - Allow getting relay states;
0 - Forbid getting relay states.

x32: (x32)\Satel
x64: (x64)\Satel

Get_Troubles

0, 1

1

4.7.4 and later

1 - Allow getting states of troubles;
0 - Forbid getting states of troubles.

x32: (x32)\Satel
x64: (x64)\Satel

Timeout

Any positive number

300

4.7.4 and later

Timeout of getting next message byte from the controller, ms.

x32: (x32)\Satel
x64: (x64)\Satel

Transmit_Cmd_Timeout

Any positive number or 0 to forbid receiving states


1000

4.7.4 and later

Rate of getting states (relay and troubles) in ms.

x32: (x32)\Satel
x64: (x64)\Satel

Verify_Link_Timeout

Any positive number

500

4.7.4 and later

Max. waiting time (ms) of getting an event from controller.
If the value is exceeded, then module considers that there is no connection with controller.

"HoneyWell N1000" (Northern Computers)     

x32: (x32)\nc

x64: (x64)\nc

bLogReact0, 114.7.4 and laterDisplaying incoming reactions in the debug window of the module and recording them to the log file.

x32: (x32)\nc

x64: (x64)\nc

bLogEvent0, 114.7.4 and laterDisplaying incoming events in the debug window of the module and recording them to the log file.

x32: (x32)\nc

x64: (x64)\nc

bLogCOM_Write0, 114.7.4 and laterDisplaying instructions sent to the terminal. Used for debugging.

x32: (x32)\nc

x64: (x64)\nc

bLogCOM_Read0, 114.7.4 and laterDisplaying transactions (events), received form the terminal, in the debug window of the module. Used for debugging.

x32: (x32)\nc

x64: (x64)\nc

bLogCOM_ReadAnswer0, 114.7.4 and laterDisplaying responses to the sent instructions in the debug window of the module. Used for debugging.

VMS (Visitor Management System)

 

 

 

 

 

x32: (x32)\id_limit
x64: (x64)\id_limit

PERSON_MINID

1-99999

-

4.7.6 and later

These keys are created to generate disjoint IDs of objects on different computers.
PERSON_MINID - PERSON_MAXID – allowed range of user IDs to edit access control service.
If PERSON_Restrict = 0, then keys are not active.

x32: (x32)\id_limit
x64: (x64)\id_limit
PERSON_MAXID1-99999-4.7.6 and later
x32: (x32)\id_limit
x64: (x64)\id_limit
PERSON_Restrict0, 104.7.6 and later
Photo ID     

x32: (x32)\

x64: (x64)\

Note. If this section has not been created, then the system will look for the key in the section.

HKEY_CURRENT_USER\Software\ITV\INTELLECT\

 NOT_DELETE_PHOTO 0, 1 0 ACFA 6.0

In ACFA 5.4 and later versions it is possible to delete irrelevant photos in the Photo identification module: when the Photo identification module gets an event and if there is no photo on the Server that gets the event, then this photo is considered irrelevant and the clients connected to the Server get a command to delete the photo.

They key allows keeping irrelevant photos on the computer where the key value is 1.

0 – delete irrelevant photos on the computer.

1 – do not delete irrelevant photos on the computer.

Access Manager




x32 and x64: HKEY_CURRENT_USER\Software\ITV\INTELLECT\Account Manager(n*)\Folder name GUID**

Note 1. n* is Access Manager object ID in Intellect.

Note 2. Folder name GUID** is automatically generated. If Intellect is run with no authorization (i.e. no login or password entered at start), folder name is zero GUID, i.e. 00000000-0000-0000-0000-000000000000. If Intellect is run with authorization, folder name is this user's GUID, e.g. 3bf041df-8b39-e711-80b7-c0bfc074aae0.
ApplyOnEnter>=0-ACFA 6.5

The key enables confirmation (OK) by Enter in Full name of new user and Edit card dialog boxes.

0 – nothing happens when pressing Enter in these dialog boxes.

>0 – pressing Enter is equal to clicking OK in Full name of new user and Edit card dialog boxes.

x32 and x64: HKEY_CURRENT_USER\Software\ITV\INTELLECT\Account Manager(n*)\Folder name GUID**

Note 1. n* is Access Manager object ID in Intellect.

Note 2. Folder name GUID** is automatically generated. If Intellect is run with no authorization (i.e. no login or password entered at start), folder name is zero GUID, i.e. 00000000-0000-0000-0000-000000000000. If Intellect is run with authorization, folder name is this user's GUID, e.g. 3bf041df-8b39-e711-80b7-c0bfc074aae0.
RotateAngle0, 1, 2, 30ACFA 6.5

The key sets rotation angle for the template while printing.

0 – 0 degrees

1 – 90 degrees

2 – 180 degrees

3 – 270 degrees

Bolid SDK Orion v.2

x32: (x32)\SDKOrion

x64: (x64)\SDKOrion

AllUsersInDevices0, 10ACFA 6.0

The key specifies default value of the Save in device checkbox:

0 – checkbox is removed on default while user creation.

1 – checkbox is set on default while user creation.

x32: (x32)\SDKOrion

x64: (x64)\SDKOrion

SkipUnusedInputs0, 10ACFA 6.0

The key is in use if it's required to add only configured (not disabled) loops on the dual loop controller while automatic search and configuring of integration objects.

0 – disabled loops are adding to hardware tree.

1 – disabled loops are not adding to hardware tree.

TABLE OF CONTENTS