When connecting the AGRG-IO-16/8-WD-DS sensor-relay cards, the electrical and technical specifications shown in the table below should be considered.

ParameterSpecification
Galvanic isolation on inputs/outputs

3750 V

Inputs

Quantity - 16

Type - current loop

Galvanic isolation - Yes

Maximum voltage - 60 V

Rated voltage - 12 V

Maximum current - 60 mA

Outputs

Quantity - 8

Type - open collector

Galvanic isolation - Yes

Maximum voltage - 300 V

Maximum current - 150 mA

Minimum pick-up voltage - 1.0 V

Minimum pick-up current - 5 mA

Reset Timer (Watchdog)Customizable
Ping interval of all alarm inputs100 ms for all contacts. Customizable
PC connection interfaceUSB 2.0, up to 5 meters
Power supply500 mA consumption from USB port