By default, for the Access Control and Detection Tools alarm groups, no data is sent from Agent Of Control. These alarm groups, as well as Hardware and Fire/Security System, can be used for designating their respective alarm types.

To classify events of an object as belonging to a particular alarm group, create an object (if it does not exist already) in the device tree. For example, if you want for the signal from the Motion detection tool to be displayed in Monitoring PSIM in the Detection Tools alarm group, create a Detector zone object and configure it (select the motion type, specify the detection area and sensitivity, etc.; for more details, see Axxon PSIM Software Package: Administrator's Guide).

To associate the events with particular alarm groups, do the following:

  1. Go to the configuration panel for the Partition Of Control object.
  2. Click the Monitoring... button. The Add/Edit events for Monitoring window opens.
  3. To add an event, click the Add... button. The event configuration window opens.
  4. In the form that appears, from the Type drop-down list (1), select the type of device. This list contains the types of all objects created on the Hardware tab of the System settings window that have recorded events.
    Example: In the case of the Motion detection tool, select the Detector zone type.
  5. From the Number drop-down list (2), select an ID number for the object of the selected type from which you want to get events. If you want to get events from all devices of this type, leave this field blank.
  6. From the Event drop-down list (3), select the event type. The available event types depend on the selected object type. System type of the event in brackets is used in scripts and programs (see Guide for creating scripts (programming) and The Script object. Programming using the JScript language).
    For example, for the Motion detection tool triggering event, select Alarm in the zone (MD_START).
  7. From the Group of alarms drop-down list (4), select an alarm group and indicate in which alarm group you want for Monitoring PSIM to display alarms for this event.
  8. It is possible to get confirmation of alarm acceptance from the Server of Control. To do this, from the Confirmation drop-down list (5), select the type of confirmation:

    1. No — no confirmation is sent.
    2. Simple Agent of Control sends confirmation when an alarm is confirmed by the operator.
    1. Complex — when accepting an alarm the operator must confirm it in the confirm box and after that the confirmation is sent.

    Note

  9. If it is necessary to attach video data to alarms, click the Video data button (6). As a result, the Select configurations for video data transmitted window will open.

    Note

    Configuration of the transmitted video data is described in Setting up the configurations for transferred video data.

    1. Move the required configurations using the button (1) from the left list to the right. Remove a configuration from the right list to the left one by using the button (2).

      Attention!

      Multiple configurations cannot be used for the same camera.

    2. Click the Apply changes and close button (3). The selected configurations will be listed in the non-editable Video data field.
  10. To add the possibility of attaching a snapshot not associated with the camera to an event, set the Get snapshot from external device checkbox (7). This way you can transmit, for example, a JPG snapshot received from an X-ray apparatus.

    Attention!

    To enable the Get snapshot from external device setting, the imageBase64<> substring with an image encoded in it must be present in the monitored event.

    Example of an image received from an external device.

  11. In the Message field (8), enter the text message, that will appear in the Device column of the Reaction to alarm dialog form (see Monitoring PSIM Software Package: Operator's Guide).

    If the object identifier is not specified, the following variables can be used in the Message field to detail the message:

    1. <id> — identifier of the object from which the event came.

    2. <name> — the object name.

      Attention!

      <id> and <name> are to be in lower case.

      After substitution of variables values the message must not be longer than 60 characters. If the resulting message is longer, extra characters will be dropped.

      Example.

      When the Disarmed event appears at the Camera 1, the Camera 1 disarmed message is sent.
  12. To search for additional information in messages from a device of this type (for the substring "param0<>"), set the Capture detailed data checkbox (9).
  13. Click the OK button to save the changes (10).

This means that when integrating a new device into Axxon PSIM, if a developer wants to be able to send more detailed information to Monitoring PSIM, when generating an event from the device, the developer should add detail in the param0<> parameter. For example, if there is a Motherboard Control module that has the Alarm event, the following values could be included in param0<>: "processor cooler", "BIOS battery", etc. If you enter Motherboard in the Message field and select Capture detailed data, the following text may appear in the Device column of the Reaction to alarm dialog form: Motherboard (CPU cooler).

Similarly, it is possible to monitor messages from other objects created in the Axxon PSIM device tree, on the Hardware tab.

Configuration for associating events with certain alarm groups is now complete.